Kit Sheet Enquire

GTJ/1112 · GTJ/2436

GTJ transition joint: PILC to XLPE

Paper, lead and steel on one side of the ferrule; XLPE and a copper screen on the other, and one kit has to satisfy both.

The job that puts a GTJ on the requisition

Nobody picks this kit off a blank sheet. It arrives because there is already paper cable in the ground. An old paper-insulated lead-covered feeder gets extended to a new substation, diverted round a road widening, or repaired after a dig-in — and the length going back in is XLPE. Where the two runs meet, two constructions have to be reconciled inside one splice.

Make off the paper side and you have oil-impregnated paper, a lead sheath and steel armour under jute. Make off the XLPE side and you have extruded insulation, a semi-conducting screen, a copper screen and a PVC oversheath. The earth reference is established differently at each end, and the paper side goes on pushing oil towards the new cable for as long as the joint stands.

So a GTJ is not a straight joint with an extra sleeve dropped in — its bill of material is drawn against two cables at once. GTJ/1112 covers systems to 12 kV; GTJ/2436 carries the 24 kV and 36 kV classes in one series. Both are published for three-core cable on both sides. If either end is single core, no GTJ code applies: that is GXSS/1236, one construction on both sides. Two ends of the same paper cable are a GPS joint, never a GTJ.

GTJ transition joint kit

GTJ transition joint kit

Heat-shrink transition joint kit for three-core cable, paper-insulated lead-covered on one side and XLPE on the other. Two series cover 12 kV, 15–24 kV and 36 kV, and each ships as a numbered bill of material rather than as a moulded body.

  • Inline connector, barrier type — three per kit on both series
  • Heat-shrink oil barrier sleeve — three per kit on both series
  • High permittivity void filler and an EPDM insulating wedge, one of each
  • Metallic protection case or wraparound joint case, with GI mesh tape published as the alternative
  • Tinned copper earth braid, tinned copper mesh tape and plumbing metal for the lead-sheath earth
SeriesGTJ/1112 and GTJ/2436
Constructions joined3-core PILC to 3-core XLPE
Voltage classes12 kV · 15–24 kV (8.7/15, 11/11, 12.7/22 kV) · 36 kV (19/33 kV)
Conductor range3x16–35 to 3x630 sq mm at 12 kV; 25–500 sq mm at 15–24 kV; 35–400 sq mm at 36 kV
Kit codesGTJ-11 to GTJ-17 · GTJ-21 to GTJ-25 · GTJ-31 to GTJ-34
In the carton20 numbered kit components plus 8 installation aids
Cable drawn against the kit11 numbered cable components on the GTJ/1112 sheet, 12 on GTJ/2436

The cable side, numbered — what the kit is matched against

No.GTJ/1112 — 12 kVNo.GTJ/2436 — 24 and 36 kV
21XLPE side: PVC outer sheath21XLPE side: XLPE cable outer sheath
22Armour22Armour
23Inner sheath23Inner sheath
24XLPE insulation24XLPE insulation
25Conductor25Semi-conducting screen
26Semi-con layer26Copper screen
27PILC side: paper insulation cover27Conductor
28Paper belting (inner sheath)28PILC side: paper insulation
29Lead sheath29Paper inner sheath
30Steel armour30Lead sheath
31Jute-impregnated outer sheath31Steel armour
32Paper cable outer sheath

Callouts from 21 upwards on the manufacturer's cross-section are the cable, not the kit. Nothing in this table ships in a carton. It is here because on a transition joint the two halves of it are the reason the kit exists.

Read the two cable lists before you read the kit list

The 12 kV drawing gives the XLPE side a semi-con layer and stops. The 24 and 36 kV drawing names a semi-conducting screen and a copper screen as separate items — a second earth path arriving at the joint, which is why the higher-class kit reworks its stress-control items rather than adding more of them. The paper side moves too: belting is named as the inner sheath at 12 kV and is gone above it, replaced by a paper inner sheath and a twelfth callout for the paper outer sheath. Check the old cable against the drawing for your class before a code goes on a schedule.

Kit contents: GTJ/1112 against GTJ/2436, item by item

No.ComponentGTJ/1112GTJ/2436
1Inline connector (barrier type)3 Nos.3 Nos.
2Stress relief mastic6 Nos.6 Nos.
3Heat-shrink oil barrier sleeve3 Nos.3 Nos.
4Conducting tubing (GTJ/1112) / semi-conducting tubing (GTJ/2436)3 Nos.1 No.
5High permittivity void filler1 No.1 No.
6Heat-shrink conducting breakout1 No.1 No.
7Stress relief / stress control mastic at the XLPE semi-con cut end6 Pcs.6 Nos.
8Heat-shrink stress control tubing3 Nos.3 Nos.
9Heat-shrink insulation tubings — 6 at 15–24 kV, 9 at 36 kV3 Nos.16 Nos.
10Heat-shrink screened tubing, dual wall (or separate insulation and conducting tubings)3 Nos.3 Nos.
11Heat-shrink compression tubings3 Nos.3 Nos.
12Metallic protection case / wraparound joint case (or GI mesh tape)1 No.1 No.
13Heat-shrink adhesive-lined side sleeve2 Nos.2 Nos.
14Insulating wedge, EPDM1 No.1 No.
15Tinned copper mesh tape3 Nos.3 Nos.
16Tinned copper earth braid1 No.1 No.
17Constant face spring clamp (or solder and flux)1 Set1 Set
18Jubilee clamps6 Nos.2 Nos.
19Heat-shrink outer jacketing tubing (centre)1 No.1 No.
20Plumbing metal1 Set1 Set

Item numbers and part names as the two sheets print them. Every part class is written up on the kit contents page; the tubings and sleeves alone are on the sleeves page.

Two items are the transition, and three lines move underneath them

Item 1 and item 3 are the transition itself. A barrier-type inline connector at the ferrule position, three per kit, and a heat-shrink oil barrier sleeve, also three per kit, on both series. Of every joint sheet in this range only the two GTJ lists name a barrier connector — GXLT, GXS, GXSS and GPS all take a plain crimping ferrule. Oil out of the paper has nowhere useful to go inside extruded insulation, and those two items are what stop it getting there.

Item 4 is where the two kits part company outright: three lengths of conducting tubing at 12 kV, one length of semi-conducting tubing at 24 and 36 kV. Item 18 moves the other way — six jubilee clamps against two. Count against the sheet for your class, never against the three letters on the label.

Item 9 is the line to query before it reaches a tender; the counting is set out on the kit contents page, and the tubings themselves on the sleeves page. Where each one lands in the build order is the installation sequence — every sleeve goes on before the crimp, and on this joint that means threading them past two different oversheaths.

Installation aids, part of the standard kit

No.Installation aidQty.
1Nylon string for cutting XLPE insulation1 No.
2Aloxite emery tape3 Pcs.
3Mopping cloth1 Pc.
4Silicone grease3 Pcs.
5Cleaning tissue6 Pcs.
6Mastic sealing tape2 Nos.
7Copper binding wire1 Roll
8Instruction manual1 No.

Identical on both GTJ sheets. These are consumed on the shift and still carry quantities, so a short carton is a short carton.

Withstand values, by class

TestGTJ/1112 — 12 kVGTJ/2436 — 15–24 kVGTJ/2436 — 36 kV
System voltages namedup to 12 kV8.7/15, 11/11, 12.7/22 kV19/33 kV
AC withstand voltage35 kV / 1 minute50 kV / 1 minute75 kV / 1 minute
DC voltage withstand48 kV / 30 minutes96 kV / 30 minutes144 kV / 30 minutes
Lightning impulse withstand75 kV required, 95 kV typical125 kV170 kV

The GTJ/1112 sheet prints a requirement column and a typical column; the GTJ/2436 sheet prints one figure per class. Both are reproduced as printed.

Ordering: conductor size in, kit code out

SeriesClassConductor size (sq mm)Kit code
GTJ/111212 kV3x16–35GTJ-11
GTJ/111212 kV3x50–95GTJ-12
GTJ/111212 kV3x120–185GTJ-13
GTJ/111212 kV3x240–300GTJ-14
GTJ/111212 kV3x400–500GTJ-15
GTJ/111212 kV3x630GTJ-17
GTJ/243615–24 kV25–50GTJ-21
GTJ/243615–24 kV70–95GTJ-22
GTJ/243615–24 kV120–150GTJ-23
GTJ/243615–24 kV185–300GTJ-24
GTJ/243615–24 kV400–500GTJ-25
GTJ/243636 kV35–70GTJ-31
GTJ/243636 kV95–150GTJ-32
GTJ/243636 kV185–300GTJ-33
GTJ/243636 kV400GTJ-34

GTJ/1112 prints its bands with the core count in front (3x16–35); GTJ/2436 prints bare figures under a heading that already says three-core. There is no GTJ-16 on the chart — the 12 kV series steps from GTJ-15 to GTJ-17. The same codes sit beside the other four series on the size charts.

The web page and the catalogue disagree on what a GTJ is for

The manufacturer's GTJ/1112 product page lists branch joints and PILC cable accessories among the series applications, beside transition jointing. The catalogue prints transition jointing only, on both GTJ charts, and its closing note reads full kit contents for making a Transition joint. Neither kit list carries a part drawn as a tee. If a GTJ code is going on a branch requisition, get the application confirmed in writing first — what a tee off a live run actually needs is on branch and tee joints.

No source for that

Dimensions. Neither GTJ chart prints a length, a diameter or a cable OD window, and the cross-section is unscaled. Selection runs on conductor area alone. Setting-out and cut-back lengths. Not on the chart, not on the drawing — they sit in the instruction manual that ships as aid number 8, and that is not published. A standard against the withstand figures. The GTJ tables are headed only Requirement and Typical Value, and cite no IEC, IS or ESI clause. A CPRI certificate dated August 2012 covers 33 kV heat-shrink joints and terminations from this manufacturer, but that is a company-level record and neither GTJ sheet refers to it. Anything commercial. No price, no lead time, no minimum order, no stock position. Kit Sheet sells nothing.

Getting a GTJ code back in one reply

Describe both cables, not one. Construction and core count each side, conductor area in sq mm, and the system voltage as the sheet writes it — 8.7/15, 11/11, 12.7/22 or 19/33 kV. Say which paper construction the old side is: the 12 kV drawing expects belting, the 24 and 36 kV drawing does not.